电力网络60秒波动之谜已解开
Mystery of 60-Second Fluctuations in Power Grids Solved

原始链接: https://www.fz-juelich.de/en/news/archive/press-release/2026/mystery-of-60-second-fluctuations-in-power-grids-solved

**摘要:** 由于利希研究中心的Dirk Witthaut领导的团队确定了全球电网每60秒出现的短暂、规律电力需求尖峰的原因。发表于《自然·能源》的研究发现,用于确保不间断供电的大规模电池储能系统会在每分钟开始时同时检查其充电状态,从而产生同步的电力消耗波动。这在于利希校园Living Lab Energy Campus的80个测量点得到确认。 这些周期性尖峰会导致水轮机瞬间减速,增加磨损。影响正在扩大:在爱尔兰,拥有大规模电池储能的数据中心约占电力需求的五分之一,该信号的振幅在2016年至2021年间增长了四倍。研究人员怀疑其他数字控制设备也可能产生类似影响。 提出的解决方案很简单:将这些检查的时间随机分布,而不是在同一时刻同步进行,从而减少电网的集体压力并延长设备寿命。

一篇 Hacker News 帖子链接到 FZ Jülich 一篇关于解决 60 秒电网波动之谜的文章。评论者将这种效应比作水锤,指出同步切换大型负载会加剧电网压力。有人指出这就是为什么数据中心重启应错峰进行。另一人表示电网负载通常随机化,但毫秒级协调的大规模切换——尤其是配合电池储能——可能产生巨大浪涌并挑战涡轮机稳定性,尽管电池本应有所帮助。该评论认为,由于电网运营商有影响力,这个问题可能会很快修复。
相关文章

原文

30 October 2026

Why do our grids show a brief spike in electricity demand every minute? A team led by Dirk Witthaut from Forschungszentrum Jülich has now demonstrated that this is due to regular power checks carried out by large-scale battery storage systems. These findings could help to make our electricity supply more robust, as the team reports in an article published in Nature Energy.

Tennet Germany, the largest transmission system operator in Germany, has observed over several years that the frequency in the European power grid dips briefly every 60 seconds. While these deviations were not critical to grid security, they were clearly measurable and unusually regular. The cause of this phenomenon was initially unclear.

A team from Jülich led by Dirk Witthaut, together with researchers from the University of Cologne and the Karlsruhe Institute of Technology, set out to investigate – and found the answer: the cause appears to be the many large-scale battery storage systems that check their state of charge every minute. This leads to measurable fluctuations in electricity consumption, which can contribute to turbine wear and tear, for example. The battery storage systems ensure an uninterrupted power supply, and their numbers have increased significantly worldwide in recent years. The researchers found that this was not a European phenomenon, but a global one.

Many devices, a common rhythm

“It really was years of detective work,” says Witthaut. The grid frequency pattern is shaped by many different factors. For example, it reveals the influence of electricity trading, with power stations being switched on and off abruptly, as well as the fluctuating feed-in from renewable energy sources, and various other disturbances.

Uns war schnell klar, dass es sich bei der Ursache um etwas handeln muss, das von der Uhr gesteuert wird

“It quickly became clear to us that the cause must be something controlled by the clock,” says Witthaut. There was no other way to explain the precise 60-second cycle. It was also clear that: “The observed effect can only be produced if many devices are consuming electricity at the same time.” A single consumer or generator could therefore be ruled out.

Measurements on campus provide the clue

But how do all these devices synchronize their consumption? The researchers finally found the crucial clues with the help of the Living Lab Energy Campus. This research infrastructure on the Jülich campus is primarily used to develop and test highly integrated energy supply systems. The team installed measuring points on end devices at a total of 80 locations – and sure enough, the same periodic pattern in electricity consumption was observed precisely at the locations where large-scale battery storage systems are designed to ensure an uninterrupted power supply. “We took a closer look at one of them and found a spike in electricity consumption at the start of every minute due to the power check,” explains Witthaut.

As there are no binding standards for such power checks, Witthaut suspects that most battery manufacturers assumed that a 60-second interval would be sensible. The start of every minute was simply chosen as the test time. “It is entirely possible, however, that battery storage systems are only part of the problem here,” says Witthaut. “It cannot be ruled out that other digitally controlled appliances – such as air-conditioning systems, heat pumps, washing machines, and dishwashers – may also exhibit similar patterns.”

Less synchronization, less wear and tear

The periodic fluctuations in electricity demand are already having an impact on hydroelectric power stations. The brief spikes in demand mean that the turbines slow down momentarily before accelerating back to their original rotational speed. This increases wear and tear. With the expansion of storage technologies, such problems could become even more prevalent. In Ireland, for example, where data centres with large-scale battery storage systems currently account for around a fifth of the country’s electricity demand, the amplitude of the 1-minute signal quadrupled between 2016 and 2021. The solution, however, would be simple: “You would simply have to distribute the checks randomly, rather than always starting them at the same time,” says Witthaut.

Original publication: 'One-minute frequency disturbances from unintended synchronization in cyber–physical power systems', Nature Energy 2026, DOI: 10.1038/s41560-026-02144-0

Contact

  • Institute of Climate and Energy Systems (ICE)
  • Energy Systems Engineering (ICE-1)
  • Institute of Climate and Energy Systems (ICE)
  • Energy Systems Engineering (ICE-1)