美国国家标准与技术研究院博尔德实验室的网络时间协议服务器已断电。
NTP at NIST Boulder Has Lost Power

原始链接: https://lists.nanog.org/archives/list/[email protected]/message/ACADD3NKOG2QRWZ56OSNNG7UIEKKTZXL/

## NIST 时间服务中断 - 科罗拉多州博尔德 NIST博尔德校区自2025年12月17日起因强风和防火措施经历长时间停电。这导致原子集成时间标出现故障,影响了博尔德互联网时间服务的准确性。 虽然服务器(time-a-b.nist.gov 至 time-e-b.nist.gov,以及 ntp-b.nist.gov)目前正在发电机供电下运行,但NIST计划禁用它们以防止发布不准确的时间。 主要问题是通过寻找替代电源来保护氢原子钟超出其电池备份的时间。校园访问仅限于紧急人员,阻碍了维修估算和监控能力。NIST希望在稳定性恢复后,使用来自另一栋建筑物中的备份时钟来恢复时间标,避免依赖外部参考。

## NIST博尔德电力中断影响时间服务 科罗拉多州博尔德市的NIST(美国国家标准与技术研究院)校园发生电力中断,导致12月19日关闭,影响了对该设施的访问。虽然WWV时间信号仍然运行,但此次中断引发了对网络时间协议(NTP)的担忧——这是一个同步计算机时钟的关键系统。 Hacker News上的用户正在讨论潜在的影响,从轻微中断到类似于Y2K的潜在重大问题,尽管许多人认为已经采取了保障措施以防止广泛故障。此次中断归因于该地区的火灾风险升高。 目前,NIST的主网站没有专门的公告,而是将用户引导至社交媒体以获取更新。截至12月20日,情况仍在持续,校园仍然关闭。
相关文章

原文

reposting from the Internet time service list [email protected] <[email protected]>: Dec 19 05:18PM -0800 Dear colleagues, In short, the atomic ensemble time scale at our Boulder campus has failed due to a prolonged utility power outage. One impact is that the Boulder Internet Time Services no longer have an accurate time reference. At time of writing the Boulder servers are still available due a standby power generator, but I will attempt to disable them to avoid disseminating incorrect time. The affected servers are: time-a-b.nist.gov time-b-b.nist.gov time-c-b.nist.gov time-d-b.nist.gov time-e-b.nist.gov ntp-b.nist.gov (authenticated NTP) No time to repair estimate is available until we regain staff access and power. Efforts are currently focused on obtaining an alternate source of power so the hydrogen maser clocks survive beyond their battery backups. More details follow. Due to prolonged high wind gusts there have been a combination of utility power line damage and preemptive utility shutdowns (in the interest of wildfire prevention) in the Boulder, CO area. NIST's campus lost utility power Wednesday (Dec. 17 2025) around 22:23 UTC. At time of writing utility power is still off to the campus. Facility operators anticipated needing to shutdown the heat-exchange infrastructure providing air cooling to many parts of the building, including some internal networking closets. As a result, many of these too were preemptively shutdown with the result that our group lacks much of the monitoring and control capabilities we ordinarily have. Also, the site has been closed to all but emergency personnel Thursday and Friday, and at time of writing remains closed. At initial power loss, there was no immediate impact to the NIST atomic time scale or distribution services because the projects are afforded standby power generators. However, we now have strong evidence one of the crucial generators has failed. In the downstream path is the primary signal distribution chain, including to the Boulder Internet Time Service. Another campus building houses additional clocks backed up by a different power generator; if these survive it will allow us to re-align the primary time scale when site stability returns without making use of external clocks or reference signals. Best wishes, -Jeff Sherman project email: [email protected] AnneJ (watching from Edinburgh, UK)

联系我们 contact @ memedata.com